CONTACTORS
TYPE TADN
Characteristics of the field
circuit
E = Rated
nominal voltage of excitation circuit; Ec = Exciter ceiling voltage (Ec =
140%E) If = Rated nominal current of excitation circuit Kdc·If =
Medium value of the field current under armature circuit fault conditions, at
the instant of the contactor's opening; Kc·If = Peak value of the
field current under armature circuit fault conditions at the instant of the
contactor's opening; Iccf = Field current under field circuit fault
conditions with voltage = Ec; Rd = Value of the disharge resistor in
ohms.
Characteristics of the contactor
- Rated
nominal voltage Vn=E
- Rated
continuous current of main contacts In=1,1 If
- Rated
short-time voltage of main contacts V'=Ec
- Rated
maximum interrupting voltage of main contacts
Vcc=Kdc·If·Rd+E
- Rated
interrupting current of main contacts at V' (short-circuit in the field
circuit) I'cc=Iccf
- Rated
interrupting current of main contacts at Vcc (short-circuit in the armature
circuit) Icc=Kdc·If+E/Rd
- Rated 1/2
second short-time current of the main contacts Icc0,5=Iccf
- Rated
interrupting current of the disharge contacts at V'
Iccd=Ec/Rd
- Rated making
current of the disharge contacts (short-circuit in the armature circuit)
Ichd=Kc·If+Ec/Rd
- Rated 15
seconds short-time current of the discharge contacts Id15''
|